Index 2 (parameter area):
0: 1 ... 9999
1: 10000 ... 19999
2: 20000 ... 29999
3: 30000 ... 39999
Index: [0] = Drive object number
[1] = Sub-index range
[2] = Parameter range
Description: Sets the drive behavior if a CAN communication error occurs.
Value: 0: No response
1: OFF1
2: OFF2
3: OFF3
Dependency: Refer to: F08700
Description: Displays the register of the CAN controller C_CAN:
Register, Message Interface Register and Message Handler Register - referred to the CAN protocol.
Index: [0] = Control register
[1] = Status register
[2] = Error counter
[3] = Bit timing register
[4] = Interrupt register
[5] = Test register
[6] = Baud rate prescaler extension register
[7] = Interface 1 command request register
[8] = Interface 1 command mask register
Note: A description of the individual registers of the C_CAN controller can be taken from "C_CAN User's Manual".
Description: Sets the CANopen NMT state that is effective after booting.
Value: 4: Stopped
5: Operational
127: Pre-operational
Dependency: Refer to: p8685
Note: Booting in the NMT state pre-operational corresponds to the CANopen standard
p8641 CAN Abort Connection Option Code / Abort con opt code
CU230P-2_CAN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 3
r8680[0...36] CAN Diagnosis Hardware / Diagnostics HW
CU230P-2_CAN Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p8684 CAN NMT state after booting / NMT state aft boot
CU230P-2_CAN Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
4 127 127