User Manual

List of parameters
Parameters
1-323
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the maximum dwell time for the energy-saving mode.
Index: [0] = Reserved
[1] = Mode 2
Note: Pe: PROFIenergy profiles
Description: Sets the general properties for energy-saving.
Note: Pe: PROFIenergy profiles
Description: Sets the mode-dependent properties for energy-saving.
Index: [0] = Reserved
[1] = Mode 2
Note: Pe: PROFIenergy profiles
Description: Display and binector output for the state display PROFIenergy energy saving active or inactive.
Note: Bit 0 and bit 1 are inverse of one another.
Pe: PROFIenergy profiles
p5606[0...1] Pe energy-saving mode dwell time maximum / Pe t_dwell max
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 4294967295 [ms] 4294967295 [ms]
p5611 Pe energy-saving properties general / Pe properties gen
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Inhibit PROFIenergy Yes No -
01 Drive initiates OFF1 Yes No -
02 Trans into energy-saving mode from PRO-
FIdrive state S4 poss
Yes No -
p5612[0...1] Pe energy-saving properties mode-dependent / Pe properties mod
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - [0] 0110 bin
[1] 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Reserved Yes No -
r5613.0...1 CO/BO: Pe energy-saving active/inactive / Pe save act/inact
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Pe active Yes No -
01 Pe inactive Yes No -