User Manual
List of parameters
Parameters
1-321
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Dependency: Refer to: r4022
Note: DI: Digital Input
Description: Displays the status of the digital outputs of Power Module 330 (PM330).
Note: DO: Digital Output
Description: Sets the simulation mode for digital inputs of the PM330 power unit.
Dependency: The setpoint for the input signals is specified using p4096.
Refer to: p4096
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.1, external alarm) High Low -
01 DI 1 (X9.2, external fault) High Low -
02 DI 2 (X9.3, Emergency Off category 1) High Low -
03 DI 3 (X9.4, Emergency Off category 0) High Low -
r4047 PM330 digital outputs status / PM330 DO status
CU230P-2_BT
(PM330)
CU230P-2_CAN
(PM330)
CU230P-2_DP
(PM330)
CU230P-2_HVAC
(PM330)
CU230P-2_PN
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X9.6: enable signal UDC link
charged)
High Low -
01 DO 1 (X9.7/X9.8: main contactor control) High Low -
p4095 PM330 digital inputs simulation mode / PM330 DI sim_mode
CU230P-2_BT
(PM330)
CU230P-2_CAN
(PM330)
CU230P-2_DP
(PM330)
CU230P-2_HVAC
(PM330)
CU230P-2_PN
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.1, external alarm) Simulation Terminal eval -
01 DI 1 (X9.2, external fault) Simulation Terminal eval -
02 DI 2 (X9.3, Emergency Off category 0) Simulation Terminal eval -
03 DI 3 (X9.4, Emergency Off category 1) Simulation Terminal eval -