Description: Displays the operating hours for the external motors.
The display can only be reset to zero.
Index: [0] = Motor 1
[1] = Motor 2
[2] = Motor 3
Description: Time limit for the continuous operation of external motors.
Continuous operation is measured starting from when a motor is connected to the line voltage. It ends when a
motor is disconnected from the line.
Description: Limit for the total operating time of external motors.
The total operating time of an external motor increases every time it is switched in.
Description: Selection of the response used to stop the motors when the OFF command is sent.
Re p2383 = 1:
OFF1 disconnects the external motors from the line in the order 3 - 2 - 1. The time set in p2387 is applied as a delay
time between the disconnection of each motor. The main motor is only switched off if all the external motors have
already been switched off.
In the case of OFF2 and OFF3, the external motors and the main motor are switched off immediately with the OFF
command (same behavior as with p2383 = 0).
Value: 0: Normal stop
1: Sequential stop
Caution: If p2383 = 1 and the OFF1 command is pending, the main motor will not be stopped until all external motors have
been disconnected and time p2387 has elapsed. The disconnection of the external motors can also serve as a
means to re-accelerate the main motor.
p2380[0...2] Closed-loop cascade control operating hours / Csc_ctrl op_hrs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [h] 340.28235E36 [h] 0.0 [h]
p2381 Closed-loop cascade control max. time for continuous operation / Csc_ctrl t_max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.1 [h] 100000.0 [h] 24.0 [h]
p2382 Closed-loop cascade control operating time limit / Csc_ctrl t_max op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.1 [h] 100000.0 [h] 24.0 [h]
p2383 Closed-loop cascade control switch-out sequence / Csc_ctr sw-out seq
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0