SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2222, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2223
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2222
Description: Displays the selected and effective fixed value of the technology controller.
Dependency: Refer to: r2229
Description: Displays the status word for the fixed value selection of the technology controller.
p2221[0...n] BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7950
Min Max Factory setting
- - 0
p2222[0...n] BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7950
Min Max Factory setting
- - 0
p2223[0...n] BI: Technology controller fixed value selection bit 3 / Tec_ctrl sel bit 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7950
Min Max Factory setting
- - 0
r2224 CO: Technology controller fixed value effective / Tec_ctr FixVal eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950
Min Max Factory setting
- [%] - [%] - [%]
r2225.0 CO/BO: Technology controller fixed value selection status word / Tec_ctr FixVal ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller fixed value selected Yes No 7950,
7951