SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the communication parameters for BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Index: [0] = Device object instance number
[1] = Maximum number of info frames
[2] = Number of APDU retries
[3] = Maximum master address
Dependency: Refer to: p2030
Description: Sets BACnet COV (change of value) increment values.
Index: [0] = Analog input 0
[1] = Analog input 1
[2] = Analog input 2
[3] = Analog input 3
[4] = Analog input 4
[5] = Analog input 5
[6] = Analog input 6
[7] = Analog input 7
[8] = Analog Output 0
Dependency: Refer to: p2030
Description: Sets the language for the BACnet object properties.
Value: 0: German
1: English
Note: Changes only become effective after POWER ON.
p2025[0...3] Fieldbus interface BACnet settings / BACnet setting
CU230P-2_BT
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4194303 [0] 1
[1] 1
[2] 3
[3] 127
p2026[0...74] Fieldbus interface BACnet COV increment / BACnet COV incr
CU230P-2_BT
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4194303 1
p2027 Fieldbus interface BACnet language selection / BACnet language
CU230P-2_BT
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0