User Manual

List of parameters
Parameters
1-233
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
If p2030 = 8 (P1), the following applies:
Min./max./factory setting: 1/99/99
Description: Sets the number of 16-bit words in the PZD part of the USS telegram for the field bus interface.
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value: 0: PKW 0 words
3: PKW 3 words
4: PKW 4 words
127: PKW variable
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Sets the time values for the fieldbus interface.
The following applies for MODBUS:
p2024[0]: Maximum permissible telegram processing time of the MODBUS slave in which a reply is sent back to the
MODBUS master.
p2024[1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
The following applies for BACnet:
p2024[0]: APDU timeout.
p2024[1, 2]: Not relevant.
Index: [0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency: Refer to: p2020, p2030
Note: Re p2024[2] (MODBUS):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
p2022 Field bus int USS PZD no. / Field bus USS PZD
CU230P-2_BT
CU230P-2_HVAC
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 8 2
p2023 Field bus int USS PKW no. / Field bus USS PKW
CU230P-2_BT
CU230P-2_HVAC
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 127 127
p2024[0...2] Fieldbus interface times / Fieldbus times
CU230P-2_BT
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 10000 [ms] [0] 1000 [ms]
[1] 0 [ms]
[2] 0 [ms]