User Manual
List of parameters
Parameters
1-229
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the reference quantity for currents.
All currents specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency: This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting
using p0573 = 1.
Refer to: r3996
Notice: If various DDS are used with different motor data, then the reference quantities remain the same as these are not
changed over with the DDS. The resulting conversion factor must be taken into account.
Example:
p2002 = 100 A
Reference quantity 100 A corresponds to 100 %
p0305[0] = 100 A
Rated motor current 100 A for MDS0 in DDS0 --> 100 % corresponds to 100 % of the rated motor current
p0305[1] = 50 A
Rated motor current 50 A for MDS1 in DDS1 --> 100 % corresponds to 200 % of the rated motor current
When the reference current is changed, short-term communication interruptions may occur.
Note: Preassigned value is p0640.
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
For infeed units, the rated line current, which is obtained from the rated power and parameterized rated line supply
voltage (p2002 = r0206 / p0210 / 1.73) is pre-assigned as the reference quantity.
Example:
The actual value of a phase current (r0069[0]) is connected to a test socket (e.g. p0771[0]). The actual current
value is cyclically converted into a percentage of the reference current (p2002) and output according to the param-
eterized scaling.
Description: Sets the reference quantity for torque.
All torques specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency: This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting
using p0573 = 1.
Refer to: r3996
Notice: When the reference torque is changed, short-term communication interruptions may occur.
Note: Preassigned value is 2 * p0333.
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
p2002 Reference current / I_ref
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.10 [Arms] 100000.00 [Arms] 100.00 [Arms]
p2003 Reference torque / M_ref
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: 7_2 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.01 [Nm] 20000000.00 [Nm] 1.00 [Nm]