User Manual
Parameters
List of parameters
1-220
© Siemens AG 2008 - 2013 All Rights Reserved
SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Displays the status of the test pulse evaluation.
Short-circuit test:
Bit 0: The short-circuit test was executed without any fault.
Bit 1: A phase short circuit has been detected.
Bit 2: A ground fault test was successfully performed.
Bit 3: A ground fault was detected.
Bit 4: A test pulse longer than one sampling time has occurred
Note: If the ground fault test was selected, but not successfully performed, then sufficient current will not be able to be
established during the test pulse.
Description: Sets the configuration for the motor data identification.
r1902 Test pulse evaluation status / Test puls ev stat
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Short-circuit test executed Yes No -
01 Phase short-circuit detected Yes No -
02 Ground fault test successfully performed Yes No -
03 Ground fault detected Yes No -
04 Identification pulse width greater than the
minimum pulse width
Yes No -
p1909[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000
0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measure-
ment
Yes No -
02 Rotor time constant estimate no measure-
ment
Yes No -
03 Leakage inductance estimate no measure-
ment
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activate vibration damping Yes No -
07 De-activate vibration detection Yes No -
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr measure-
ment
Yes No -
14 De-activate valve interlocking time mea-
surement
Yes No -
15 Determine only stator resistance, valve volt-
age fault, dead time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter cal-
culation
Yes No -