Description: Sets the offset voltage in the beta direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note: The value is pre-set during the rotating measurement.
Description: Displays the internal status signals of the motor model:
Index 0: Changeover ramp between current and voltage models
Index 1: Changeover ramp for model tracking (encoderless induction motors only)
Index 2: Changeover ramp for zero frequency range (encoderless induction motors only)
Index: [0] = Changeover ramp motor model
[1] = Changeover ramp model tracking
[2] = Changeover ramp zero frequency encoderless ASM
[3...6] = Reserved
Description: Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM): Rs, Lh, and offset compensation.
Dependency: In U/f characteristic operating mode only bit 7 is relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note: ASM: Induction motor
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is de-
activated and is instead taken into account in the motor model.
In order that the correction values of the Rs and Lh adaptation (selected using bit 0 ... bit 1) are correctly accepted
when changing over the drive data set, a dedicated motor number must be entered into p0826 for each different
motor.
p1775[0...n] Motor model offset voltage compensation beta / MotMod offs comp B
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]
r1776[0...6] Motor model status signals / MotMod status sig
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p1780[0...n] Motor model adaptation configuration / MotMod adapt conf
Access level: 4 Calculated: p0340 = 1,3,4 Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0001 0100 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Select motor model ASM Rs adaptation Yes No -
02 Select motor model ASM Lh adaptation Yes No -
04 Select motor model offset adaptation Yes No -
07 Select T(valve) with Rs adaptation Yes No -
10 Filter time combination current like current
ctrl integral time
Yes No -