SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the proportional gain of the current controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Description: Sets the integral-action time of the current controller.
Dependency: Refer to: p1715
Description: Sets the speed threshold for deactivating the integral component of the Isd controller. The d current controller is
only effective as P controller for speeds greater than the threshold value. Instead of the integral component, the
quadrature arm decoupling is effective.
Warning: For settings above 80%, the d current controller is active up to the field weakening limit. When operated at the volt-
age limit, this can result in an unstable behavior. In order to avoid this, the dynamic voltage reserve p1574 should
be increased.
Note: The parameter value is referred to the synchronous rated motor speed.
Description: Sets the time constant to calculate the d current DC component difference (combination current) to add to the d cur-
rent controller actual value. The additional input is de-activated with p1731 = 0.
p1715[0...n] Current controller P gain / I_ctrl Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.000 100000.000 0.000
p1717[0...n] Current controller integral-action time / I_ctrl Tn
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 1710, 5714, 6714,
7017
Min Max Factory setting
0.00 [ms] 1000.00 [ms] 2.00 [ms]
p1730[0...n] Isd controller integral component shutdown threshold / Isd_ctr I_compDeac
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
30 [%] 150 [%] 30 [%]
p1731[0...n] Isd controller combination current time component / Isd ctrl iCombi T1
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 0.00 [ms]