Note: Re bit 19, 20:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced.
Re bit 20:
The acceleration model for the speed setpoint is only active if p1496 is not zero.
Description: Sets the configuration for the closed-loop speed control.
Note: Re bit 19, 20:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced.
Re bit 20:
The acceleration model for the speed setpoint is only active if p1496 is not zero.
Description: Sets the configuration for flux setpoint control
Note: Re bit 01:
Initially, the flux is only established with a low rate of rise when magnetizing the induction motor. The flux setpoint
p1570 is reached again at the end of the magnetizing time p0346.
The flux differentiation can be switched out if a significant ripple occurs in the field-generating current setpoint
(r0075) when entering the field weakening range. However, this is not suitable for fast acceleration operations
because then, the flux decays more slowly and the voltage limiting responds.
Re bit 02:
The flux build-up control operates during the magnetizing phase p0346 of the induction motor. If it is switched out, a
constant current setpoint is injected and the flux is built up corresponding to the rotor time constant.
Re bit 06:
Magnetizing is performed with maximum current (0.9 * r0067). With active identification of the stator resistance (see
p0621) quick magnetizing is internally de-activated and alarm A07416 is displayed. During a flying restart of a rotat-
ing motor (see p1200) no quick magnetizing takes place.
p1400[0...n] Speed control configuration / n_ctrl config
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6490
Min Max Factory setting
- - 0000 0000 0011 1000 1000 0000
0010 0001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Automatic Kp/Tn adaptation active Yes No 6040
05 Kp/Tn adaptation active Yes No 6040
15 Sensorless vector control speed pre-control Yes No 6030
19 Anti-windup for integral component Yes No 6030
20 Acceleration model ON OFF 6030
21 Free Tn reduction active Yes No 6030
p1401[0...n] Flux control configuration / Flux ctrl config
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6491
Min Max Factory setting
- - 0000 0110 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Flux setpoint differentiation active Yes No 6723
02 Flux build-up control active Yes No 6722,
6723
06 Quick magnetizing Yes No 6722