SINAMICS G120 CU230P-2 Control Units List Manual (LH9), 01/2013
Description: Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note: This time can be exceeded if the DC link voltage reaches its maximum value.
Description: Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Dependency: The parameter is pre-assigned depending on the size of the power unit.
Note: This time can be exceeded if the DC link voltage reaches its maximum value.
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1135[0...n] OFF3 ramp-down time / OFF3 t_RD
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(1), U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3060, 3070
Min Max Factory setting
0.000 [s] 5400.000 [s] 0.000 [s]
p1135[0...n] OFF3 ramp-down time / OFF3 t_RD
PM330 Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(1), U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3060, 3070
Min Max Factory setting
0.000 [s] 5400.000 [s] 3.000 [s]
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM230 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
PM330 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.500 [s]
p1137[0...n] OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]