User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
609
3 Function diagrams
3.12 Free function blocks
Fig. 3-100 7200 – Sampling times of the runtime groups
- 7200 -
Function diagram
87654321
fp_7200_97_51.vsd
Free Function Blocks
G120 CU230P-2
07.04.2014 V4.7
Sampling times of the runtime groups
Run-time group
1
r20001[1] = 8 ms
RTG sampling time [ms]
r20001[0..9]
2
r20001[2] = 16 ms
3
r20001[3] = 32 ms
4
r20001[4] = 64 ms
5
r20001[5] = 128 ms
6
r20001[6] = 256 ms
Logic function blocks
AND, OR, XOR, NOT
Arithmetic function blocks
ADD, SUB, MUL, DIV, AVA, NCM, PLI
X
-
X
-
X
-
X
-
X
X
X
X
Time function blocks
MFP, PCL, PDE, PDF, PST
Memory function blocks
RSR, DSR
-
X
-
X
-
X
-
X
X
X
X
X
Switch function block
NSW
Switch function block
BSW
-
X
-
X
-
X
-
X
X
X
X
X
Control function blocks
LIM, PT1, INT, DIF
Complex function blocks
LVM
-
-
-
-
-
-
-
-
X
X
X
X