2 Parameters
2.2 List of parameters
Note: - Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the excessively
high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
- for a PM230 power unit, sizes D - F the parameter is ineffective.
Description: Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Description: Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Description: Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = Induction motor
2 = Synchronous motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
Value: 0: No motor
1: Induction motor
2: Synchronous motor
10: 1LE1 induction motor
13: 1LG6 induction motor
17: 1LA7 induction motor
19: 1LA9 induction motor
100: 1LE1 induction motor
Dependency: When selecting a motor type from the 1LE1, 1LG6, 1LA7, 1LA9 series, parameters p0335, p0626, p0627, and p0628
of the thermal motor model are pre-assigned as a function of p0307 and p0311.
Caution: If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Note: Once the Control Unit has been powered up for the first time or if the factory settings have been defined accordingly,
the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
r0296 DC link voltage undervoltage threshold / Vdc U_lower_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [V] - [V] - [V]
r0297 DC link voltage overvoltage threshold / Vdc U_upper_thresh
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8750, 8760, 8850,
8864, 8950, 8964
Min Max Factory setting
- [V] - [V] - [V]
p0300[0...n] Motor type selection / Mot type sel
PM230
PM250, PM260
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 3) Scaling: - Dyn. index: MDS, p0130
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0 100 0