2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
56 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Displays the internal resistance of the power unit (IGBT and line resistance).
Description: Sets the configuration for the output voltage measurement of the power unit.
Note: Only special power units support this function (e.g. PM330).
Re bit 01:
The controller can be set using p0245 and p0246.
Description: Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index: [0] = Threshold at which pre-charging starts
[1] = Threshold at which pre-charging stops
Dependency: Refer to: p1901
Note: This parameter is only relevant for chassis power units.
Description: Displays the actual maximum output current of the power unit taking into account derating factors.
r0238 Internal power unit resistance / PU R internal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0247 Voltage measurement configuring / U_mes config
PM330 Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(2), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0010 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate voltage measurement Yes No -
01 Siemens internal Yes No -
02 Siemens internal Yes No -
05 Use voltage measured values for flying
restart
Yes No -
07 Voltage calibration when switching on Yes No -
08 Voltage monitoring when switching on Yes No -
09 Voltage monitoring cyclic Yes No -
p0287[0...1] Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 100.0 [%] [0] 6.0 [%]
[1] 16.0 [%]
r0289 CO: Maximum power unit output current / PU I_outp max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Arms] - [Arms] - [Arms]