User Manual
2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
466 List Manual (LH9), 04/2014, A5E33838102B AA
Re p31022 = 11:
The highest value of actual values 1, 2, and 3 is used as r31027.
Description: Sets the signal source for the multi-zone control setpoints.
Description: Displays the relevant setpoint at the multi-zone control output.
Description: Sets the signal source for the day/night multi-zone control switchover.
Description: Sets the signal source for the multi-zone control actual values.
Description: Displays the relevant actual value at the multi-zone control output.
Description: Displays PROFINET Name of Station.
Notice: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
p31023[0...3] CI: Multi-zone control setpoint input / Zone_ctrl setp inp
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r31024 CO: Multi-zone control setpoint output / Zone_ctrl set outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]
p31025 BI: Multi-zone control day/night switchover / Zone_ctl day_night
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
p31026[0...2] CI: Multi-zone control actual-value input / Zon_ctrl act inp
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
r31027 CO: Multi-zone control actual-value output / Zon_ctrl act outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]
r61000[0...239] PROFINET Name of Station / PN Name of Station
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -