SINAMICS G120 CU230P-2 Control Units
464 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Setting parameter for the run-time group in which instance PLI 1 of the polyline is to be called
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance PLI 1 within the run-time group set in p20382.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Setting for interconnecting multi-zone control
Value: 0: Removing the multi-zone control interconnection
1: Interconnecting multi-zone control
Notice: When multi-zone control is interconnected, outputs r31024 and r31027 are always connected to index 0 of
parameters p2253 and p2264. Any changes made to the command data set (CDS) in p2253 and p2264 are ignored.
Note: Re p31020 = 0:
The following BICO interconnections are automatically removed:
- p31023[0] = 0
- p31023[2] = 0
- p31026[0] = 0
- p31026[1] = 0
- p2253[0] = 0
- p2264[0] = 0
Re p31020 = 1:
The following BICO interconnections are automatically established:
- p31023[0] = r0755[0]
- p31023[2] = r0755[1]
- p31026[0] = r0755[2]
- p31026[1] = r0755[3]
- p2253[0] = r31024
- p2264[0] = r31027
p20382 PLI 1 run-time group / PLI 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7226
Min Max Factory setting
5 9999 9999
p20383 PLI 1 run sequence / PLI 1 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7226
Min Max Factory setting
0 32000 990
p31020 Multi-zone control interconnection / Zone_ctrl intercon
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0