User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
44 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Display and connector output for the output frequency of the power unit.
Dependency: Refer to: r0024
Note: The output frequency is available smoothed (r0024) and unsmoothed (r0066).
For vector control and operation with encoder (p0400 > 0), the following applies:
The parameter value corresponds to the actual encoder speed.
Description: Display and connector output for the maximum output current of the power unit.
Dependency: The maximum output current is determined by the parameterized current limit and the motor and converter thermal
protection.
Refer to: p0290, p0640
Description: Displays actual absolute current.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0027
Notice: The value is updated with the current controller sampling time.
Note: Absolute current value = sqrt(Iq^2 + Id^2)
The absolute value of the current actual value is available smoothed (r0027 with 300 ms, r0068[1] with p0045) and
unsmoothed (r0068[0]).
Description: Display and connector output for the measured actual phase currents as peak value.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
[3] = Phase U offset
[4] = Phase V offset
[5] = Phase W offset
[6] = Total U, V, W
r0066 CO: Output frequency / f_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 2_1 Unit selection: p0505 Func. diagram: 6300, 6310, 6730,
6731, 6799
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r0067 CO: Output current maximum / I_outp max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: 6300, 6640, 6724
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0068[0...1] CO: Absolute current actual value / I_act abs val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: 6300, 6714, 6799,
7017, 8014, 8017, 8018
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0069[0...6] CO: Phase current actual value / I_phase act value
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_5 Unit selection: p0505 Func. diagram: 6730
Min Max Factory setting
- [A] - [A] - [A]