User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
41
2 Parameters
2.2 List of parameters
Note: The following control bits are displayed in r0054:
Bit 00: r0898 Bit 0
Bit 01: r0898 Bit 1
Bit 02: r0898 Bit 2
Bit 03: r0898 Bit 3
Bit 04: r0898 Bit 4
Bit 05: r0898 Bit 5
Bit 06: r0898 Bit 6
Bit 07: r2138 Bit 7
Bit 08: r0898 Bit 8
Bit 09: r0898 Bit 9
Bit 10: r0898 Bit 10
Bit 11: r1198 Bit 11
Bit 13: r1198 Bit 13
Bit 14: r1198 Bit 14
Bit 15: r0836 Bit 0
Description: Display and BICO output for supplementary control word.
Note: CDS: Command Data Set
DDS: Drive Data Set (DDS)
The following control bits are displayed in r0055:
Bit 00: r1198.0
Bit 01: r1198.1
Bit 02: r1198.2
Bit 03: r1198.3
Bit 04: r0837.0
Bit 05: r0837.1
Bit 08: r2349.0 (negated)
Bit 09: r1239.11
05 Continue ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master ctrl by PLC Yes No -
11 Direction reversal (setpoint) Yes No -
13 Motorized potentiometer raise Yes No -
14 Motorized potentiometer lower Yes No -
15 CDS bit 0 Yes No -
r0055.0...15 CO/BO: Supplementary control word / Suppl STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2513
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setp bit 0 Yes No -
01 Fixed setp bit 1 Yes No -
02 Fixed setp bit 2 Yes No -
03 Fixed setp bit 3 Yes No -
04 DDS select. bit 0 Yes No -
05 DDS select. bit 1 Yes No -
08 Technology controller enable Yes No -
09 DC braking enable Yes No -
11 Droop enable Yes No -
12 Torque control active Yes No -
13 External fault 1 (F07860) No Yes -
15 CDS bit 1 Yes No -