User Manual
SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
33
2 Parameters
2.2 List of parameters
Description: Displays the smoothed actual value of the active power.
Dependency: Refer to: r0082
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: Power delivered at the motor shaft.
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
Description: Displays the motor utilization from motor temperature model 1 (I2t).
Dependency: The thermal motor utilization is only determined for permanent-magnet synchronous motors when the motor
temperature model 1 (I2t) is activated.
For motor temperature model 1 (I2t) (p0612.0 = 1), the following applies:
- r0034 = (motor model temperature - 40 K) / (p0605 - 40 K) * 100 %
Refer to: p0611, p0612, p0615
Notice: After the drive is switched on, the system starts to determine the motor temperature with an assumed model value.
This means that the value for the motor utilization is only valid after a stabilization time.
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
For r0034 = -200.0 %, the following applies:
The value is invalid (e.g. the motor temperature model is not activated or has been incorrectly parameterized).
Description: Display and connector output for the actual temperature in the motor.
Note: For r0035 not equal to -200.0 °C, the following applies:
- this temperature display is valid.
- a KTY sensor is connected.
- for induction motors, the thermal motor model is activated (p0601 = 0).
For r0035 equal to -200.0 °C, the following applies:
- this temperature display is not valid (temperature sensor error).
- A PTC sensor or bimetallic NC contact is connected.
- for synchronous motors, the thermal motor model is activated (p0601 = 0).
r0032 CO: Active power actual value smoothed / P_actv_act smth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dyn. index: -
Units group: 14_10 Unit selection: p0505 Func. diagram: 5730, 6799, 8750,
8850, 8950
Min Max Factory setting
- [kW] - [kW] - [kW]
r0034 CO: Motor utilization thermal / Mot_util therm
PM230
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8017
Min Max Factory setting
- [%] - [%] - [%]
r0035 CO: Motor temperature / Mot temp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Dyn. index: -
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016, 8017
Min Max Factory setting
- [°C] - [°C] - [°C]