User Manual

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
329
2 Parameters
2.2 List of parameters
Description: Displays the PROFIenergy mode ID of the effective energy saving mode.
Value: 0: POWER OFF
2: Energy-saving mode 2
255: Ready
Note: Pe: PROFIenergy profiles
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, dwell time minimal
Index: [0] = Reserved
[1] = Mode 2
Note: It is not permissible that the value is less than the sum of the "energy-saving mode transition time" and the "operating
state transition time" (system properties).
Pe: PROFIenergy profiles
Description: Sets the maximum dwell time for the energy-saving mode.
Index: [0] = Reserved
[1] = Mode 2
Note: Pe: PROFIenergy profiles
Description: Sets the general properties for energy-saving.
r5600 Pe energy saving mode ID / Pe mode ID
CU230P-2_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2381
Min Max Factory setting
300000 [ms] 4294967295 [ms] [0] 300000 [ms]
[1] 480000 [ms]
p5606[0...1] Pe energy-saving mode dwell time maximum / Pe t_dwell max
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [ms] 4294967295 [ms] 4294967295 [ms]
p5611 Pe energy-saving properties general / Pe properties gen
CU230P-2_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Inhibit PROFIenergy control commands Yes No -
01 Drive initiates OFF1 when transitioning to
energy-saving mode
Yes No -
02 Trans into energy-saving mode from
PROFIdrive state S4 poss
Yes No -