User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
294 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the time constant for the differentiation (D component) of the technology controller.
Note: p2274 = 0: Differentiation is disabled.
Description: Sets the proportional gain (P component) of the technology controller.
Note: p2280 = 0: The proportional gain is disabled.
Description: Sets the integral time (I component, integrating time constant) of the technology controller.
Notice: The following applies for p2251 = 0:
If the output of the technology controller lies within the range of a suppression (skip) bandwidth (p1091 ... p1094,
p1101) or below the minimum speed (p1080), the integral component of the controller is held so that the controller
temporarily works as a P controller. This is necessary in order to prevent the controller from behaving in an unstable
manner, as the ramp-function generator switches to the parameterized up and down ramps (p1120, p1121) at the
same time in order to avoid setpoint steps. This state can be exited or avoided by changing the controller setpoint or
by using the start speed (= minimum speed).
Note: When the controller output reaches the limit, the I component of the controller is held.
p2285 = 0:
The integral time is disabled and the I component of the controller is reset.
Description: Sets the signal source to hold the integrator for the technology controller.
Description: Sets the signal source for the pre-control signal of the technology controller.
p2274 Technology controller differentiation time constant / Tec_ctrl D comp T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2280 Technology controller proportional gain / Tec_ctrl Kp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 1000.000 1.000
p2285 Technology controller integral time / Tec_ctrl Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 10000.000 [s] 30.000 [s]
p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ hold
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 56.13
p2289[0...n] CI: Technology controller pre-control signal / Tec_ctr prectr_sig
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0