User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
270 List Manual (LH9), 04/2014, A5E33838102B AA
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
Description: Display and BICO output for status word 1 of faults and alarms.
Note: Re bit 03, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a
change in the buffer was also detected (r0944, r9744, r2121).
Re bit 06, 08:
These status bits are used for internal diagnostic purposes only.
Re bit 11, 12:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes
only on certain automation systems with integrated SINAMICS functionality.
Description: Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency: Refer to: p2155, r2197
Description: Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes No 8060
10 External alarm 1 (A07850) effective Yes No 8065
11 External alarm 2 (A07851) effective Yes No 8065
12 External alarm 3 (A07852) effective Yes No 8065
13 External fault 1 (F07860) effective Yes No 8060
14 External fault 2 (F07861) effective Yes No 8060
15 External fault 3 (F07862) effective Yes No 8060
r2139.0...15 CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2548
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Being acknowledged Yes No -
01 Acknowledgment required Yes No -
03 Fault present Yes No 8060
06 Internal message 1 present Yes No -
07 Alarm present Yes No 8065
08 Internal message 2 present Yes No -
11 Alarm class bit 0 High Low -
12 Alarm class bit 1 High Low -
13 Maintenance required Yes No -
14 Maintenance urgently required Yes No -
15 Fault gone/can be acknowledged Yes No -
p2140[0...n] Hysteresis speed 2 / n_hysteresis 2
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8010
Min Max Factory setting
0.00 [rpm] 300.00 [rpm] 90.00 [rpm]
p2141[0...n] Speed threshold 1 / n_thresh val 1
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 8010
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 5.00 [rpm]