User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
244 List Manual (LH9), 04/2014, A5E33838102B AA
Description: The serial interface for the debug monitor is COM1 (commissioning interface, RS232) or COM2 (fieldbus interface,
RS485).
Value = 0: De-activated
Value = 1: COM1, commissioning protocol is de-activated
Value = 2: COM2, field bus is de-activated
Value = 3: Reserved
Note: Value = 2 is only possible for Control Units with RS485 as a field bus interface.
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Note: p2040 = 0:
Monitoring is de-activated.
Description: Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: Every change only becomes effective after a POWER ON.
Description: Displays the PROFIdrive PZD state.
Dependency: Refer to: p2044
p2039 Select debug monitor interface / Debug monit select
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 0
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
CU230P-2_BT
CU230P-2_HVAC
CU230P-2_PN
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 [ms] 1999999 [ms] 100 [ms]
p2042 PROFIBUS Ident Number / PB Ident No.
CU230P-2_DP Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
r2043.0...2 BO: PROFIdrive PZD state / PD PZD state
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint failure Yes No -
02 Fieldbus oper Yes No -