User Manual

SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
231
2 Parameters
2.2 List of parameters
Description: Sets the configuration of the rotating measurement.
Note: The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
Description: Sets the configuration of the rotating measurement.
Note: The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
Description: Sets the configuration of the rotating measurement.
p1959[0...n] Rotating measurement configuration / Rot meas config
PM230
PM250, PM260
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0001 1110 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller
parameters
Yes No -
04 Speed controller optimization (vibration test) Yes No -
p1959[0...n] Rotating measurement configuration / Rot meas config
PM240 Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0001 1110 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller
parameters
Yes No -
04 Speed controller optimization (vibration test) Yes No -
12 Measurement shortened Yes No -
13 After measurement direct transition into
operation
Yes No -
p1959[0...n] Rotating measurement configuration / Rot meas config
PM330 Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0001 0000 0001 1110 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller
parameters
Yes No -