SINAMICS G120 CU230P-2 Control Units
List Manual (LH9), 04/2014, A5E33838102B AA
209
2 Parameters
2.2 List of parameters
Re bit 7 = 1:
The following applies for encoderless vector control of induction motors:
If the changeover limits are parameterized too low (p1755, p1756), then they are automatically increased to rugged
values by the absolute amount p1749 * p1755.
The effective time condition for changing over into open-controlled operation is given by Min(p1758, 0.5 * r0384).
Activation can make sense for applications that demand a high torque at low frequencies and therefore low speed
gradients.
Adequate parameterization must be ensured (p1610, p1611).
Description: Sets the configuration for the motor model.
Bit 0 = 1: Forces open-loop speed-controlled starting (ASM).
Bit 1 = 1: Forces the system to pass through frequency zero, open-loop-controlled (ASM).
Bit 2 = 1: Drive remains in full closed-loop control mode, even at zero frequency (ASM).
Bit 3 = 1: Motor model evaluates the saturation characteristic (ASM).
Bit 6 = 1: If the motor is blocked, sensorless vector control remains speed-controlled (ASM).
Bit 7 = 1: Use rugged switchover limits to switchover the model (open-loop/closed-loop controlled) for regenerative
operation (ASM).
Dependency: Refer to: p0500
Caution: Do not use bit 6 = 1 if the motor can be slowly reversed by the load at the torque limit. Long delay times due to
blocking (p2177 > p1758) can cause the motor to stall. In this case you should de-activate the function or use closed-
loop control throughout the speed range (note the information re bit 2 = 1).
Note: Bits 0 ... 2 only have an influence for encoderless vector control, bit 2 is pre-assigned depending on p0500.
Re bit 2 = 1:
The sensorless vector control is effective down to zero frequency. A change is not made into the open-loop speed
controlled mode.
This operating mode is possible for passive loads. These include applications where the load itself does not generate
any active torque and therefore only acts reactively to the drive torque of the induction motor.
If bit 2 = 1, then bit 3 is automatically set to 1. Manual de-selection is possible and may be sensible if the saturation
characteristic (p1960) was not measured for third-party motors. Generally, for standard SIEMENS motors, the
already pre-assigned (default value) saturation characteristic is adequate.
When the bit is set, the selection of bits 0 and 1 is ignored.
Re bit 2 = 0:
Bit 3 is also automatically deactivated.
Re bit 6 = 1:
The following applies for encoderless vector control of induction motors:
For a blocked motor (see p2175, p2177) the time condition in p1758 is bypassed and a change is not made into
open-loop controlled operation.
Re bit 7 = 1:
The following applies for encoderless vector control of induction motors:
If the changeover limits are parameterized too low (p1755, p1756), then they are automatically increased to rugged
values by the absolute amount p1749 * p1755.
The effective time condition for changing over into open-controlled operation is given by Min(p1758, 0.5 * r0384).
p1750[0...n] Motor model configuration / MotMod config
PM240
PM250, PM260
Access level: 3 Calculated: p0340 = 1,3,5 Data type: Unsigned8
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Controlled start Yes No -
01 Controlled through 0 Hz Yes No -
02 Closed-loop ctrl oper. down to zero freq. for
passive loads
Yes No -
03 Motor model Lh_pre = f(PsiEst) Yes No -
06 Closed-loop/open-loop controlled (PEM) for
blocked motor
Yes No -
07 Use rugged changeover limits Yes No -