197
2 Parameters
2.2 List of parameters
Description: Display and connector output for the actual effective upper torque limit.
Note: The effective upper torque limit is reduced with respect to the selected upper torque limit p1520, if the current limit
p0640 is reduced or the rated magnetizing current of the induction motor p0320 is increased.
This may be the case for rotating measurements (see p1960).
The torque limit p1520 can be re-calculated using p0340 = 1, 3 or 5.
Description: Display and connector output for the actual effective lower torque limit.
Note: The effective lower torque limit is reduced with respect to the selected lower torque limit p1521, if the current limit
p0640 is reduced or the rated magnetizing current of the induction motor p0320 is increased.
This may be the case for rotating measurements (see p1960).
The torque limit p1520 can be re-calculated using p0340 = 1, 3 or 5.
Description: Displays the limit for the torque-generating current component using the stall calculation, the current limit of the
power unit as well as the parameterization in p0640.
Index: [0] = Upper limit
[1] = Lower limit
Description: Sets the scaling of the stall limit for the start of field weakening.
Danger: If the stall current limit is increased, then the q current setpoint can exceed the stall limit; as a consequence, a
hysteresis effect can occur when loading and unloading.
r1538 CO: Upper effective torque limit / M_max upper eff
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Units group: 7_1 Unit selection: p0505 Func. diagram: 6020, 6640
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r1539 CO: Lower effective torque limit / M_max lower eff
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Units group: 7_1 Unit selection: p0505 Func. diagram: 6020, 6640
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r1548[0...1] CO: Stall current limit torque-generating maximum / Isq_max stall
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1553[0...n] Stall limit scaling / Stall limit scal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
80.0 [%] 130.0 [%] 100.0 [%]