User Manual

2 Parameters
2.2 List of parameters
SINAMICS G120 CU230P-2 Control Units
156 List Manual (LH9), 04/2014, A5E33838102B AA
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency: Refer to: p1140, p1141
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency: Refer to: p1140, p1141
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
Description: Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency: The signal source for the ramp-function generator setting value is set using parameters.
Refer to: p1144
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU230P-2_BT
CU230P-2_CAN
CU230P-2_HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - 1
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
CU230P-2_DP
CU230P-2_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - [0] 2090.6
[1] 1
[2] 2090.6
[3] 2090.6
p1143[0...n] BI: Ramp-function generator, accept setting value / RFG accept set v
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
- - 0