2 Parameters
2.2 List of parameters
Note: OC: Operating condition
Description: Display and BICO output for the status word of the sequence control.
Note: Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description: Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the DIP switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if all of the DIP switches are set to ON or OFF.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
For p0014 = 0, the following applies:
Before a changed setting becomes permanently effective, a non-volatile RAM to ROM data save is required. To do
this, set p0971 = 1 or p0014 = 1.
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the send and receive telegram.
r0899.0...11 CO/BO: Status word sequence control / ZSW seq_ctrl
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2503
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Rdy for switch on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Jog active Yes No -
04 No coasting active OFF2 inactive OFF2 active -
05 No Quick Stop active OFF3 inactive OFF3 active -
06 Switching on inhibited active Yes No -
07 Drive ready Yes No -
08 Controller enable Yes No -
09 Control request Yes No -
11 Pulses enabled Yes No -
p0918 PROFIBUS address / PB address
CU230P-2_DP Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2401, 2410
Min Max Factory setting
1 126 126
p0922 PROFIdrive PZD telegram selection / PZD telegr_sel
CU230P-2_DP
CU230P-2_PN
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: C(1), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2401, 2420
Min Max Factory setting
1 999 1