User Manual

Siemens Building Technologies CE2B5378xx 15.05.2015 6
3. Operating
3.1 Operating elements
Fig. 1
Symbol Description
Identification: Previous year's value (set day value)
Identification: Previous month's value
Information
Symbol for heat meter
Symbol for cold meter
Installation site: Return-flow
Installation site: Flow
Year of manufacture
Note
: Both display range and data displayed can differ
from this description depending on the meter param
e-
teri
sation. Certain button functions can also be
blocked.
Switching the display
Please proceed as follows to switch between the display val-
ues:
Press the button briefly to show the next line of the current
loop.
The first display value will appear again after the final display
value.
Press the button for a longer time (longer than 10 s) in
order to display the service loop.
Press the button for 3 s in the service loop in order to leave
the service loop.
User loop
User loop Display type
0054567 kWh Energy accumulated
00065.43 Volume accumulated
888888 kWh Segment test Info
F - - - In case of error: message with error
code
Info
Service loop
Service loop Display type
0.534 m³/h Current flow
22.9 kW Current power
84 47 °C
Current temperature hot side / cold
side
04.06.11 D Date
786 Bh Operating hours
56 Fh Missing hours
3792701 G Device number, 7 digit Info
PulSE
CH Remote read out mode (optional) Info
123 A Primary address for M-Bus option Info
2345678 K Property number, 7 digit Info
18.02.11 F0 Date stamp for F0 early warning Info
3- 01 FW Firmware version Info
31.12.10 V Storage day previous year Previous year
0034321 kWh Energy previous year on set day Previous year
00923.12 Volumes: previous year on set day Previous year
12 Fh Missing hours previous year Previous year
- -.- -.- - C Code input for parameterisation
01.06.11 M Storage day month 1-15 Previous month
over 3s button press:
0034321 kWh Energy previous month on refer-
ence date
Previous month
00923.12 Volume previous month on refer-
ence date
Previous month
12 Fh Missing hours previous month on
reference date
Previous month
3.2 Monthly values
The meter stores the following values for 15 months on the
monthly set day
Energy (meter status)
Volume (meter status)
Missing hours (meter status)
When the meter shows the monthly set day, press the button
for 3 s in order to display the previous month's values.
You can also read the monthly values via the optical interface.
4. Functional Details
If the respective operation thresholds are exceeded and flow
and temperature difference are positive, the meter summates
the energy and the volume. All segments of the display are
switched on for control purposes during the segment test.
The meter status for energy, volume and missing time is en-
tered into a log for the previous year on an annual basis on the
annual set day.
The flow, power and temperature difference are recorded with
the appropriate +/- signs. If the operation threshold has
dropped, a "u" is displayed in front. The current temperatures
are presented together as whole numbers in °C in a display
line.
You can set the 8 digit property number (secondary address
for M-Bus operation) in the parameterising mode. The highest
value point is suppressed in the display. The device number is
issued by the manufacturer.
The operating hours are counted from the first connection of
the power supply. Missing hours are summated if there is a
fault and the meter is thus unable to take measurements. The
date is incremented on a daily basis.
The number for the firmware version is issued by the manufac-
turer.
5. Error Messages
The meter continuously runs a self-diagnosis and can thus
recognise and display various installation or meter error mes-
sages.
The error message F0 means that no flow measurement is
possible, due to air in the volume measurement unit for exam-
ple; the system must be vented carefully.
The error message F4 means the battery must be replaced.
When any of the error messages F1, F2 or F5, F6, F8 are
displayed, the temperature sensors are defective. The mes-
sages F3, F7, F9 mean a defect in the electronics.
Contact the service department in all these cases.
Button
Security seal