Data Sheet for Product

11/12
Siem ens Modulating control valves with magnetic actuator‚ PN 16 CA1N4465en
Building Technologies 2018-02-05
Connection terminals
AC / DC 24 V operating
voltage
System neutral
System potential
Positioning signal
DC 0...10 V / 2...10 V / 4...20 mA
Measuring neutral (= G0)
Position feedback signal
DC 0...10 V
Force control input
R = Inner resistance between G0 and YM, approx 10 kΩ
Connection diagrams
If controller and valve receive their power from separate sources, only one
transformer may be earthed on the secondary side.
In case of DC power supply, a 4-wire connection is mandatory!
Common transformer Separate transformer
Common transformer Separate transformer
U
Indication of valve position (only if required). DC 0...10 V 0...100 % volumetric flow V
100
Twisted pairs. If the lines for AC 24 V power supply and the DC 0...10 V (DC 2...10 V,
DC 4...20 mA) positioning signal are routed separately, the AC 24 V line need not be twisted.
Piping must be connected to potential earth!
Factory setting: Valve characteristics ‘linear’, positioning signal DC 0...10 V.
Details see «Configuration DIL switches», page 4.
See «Calibration», page 5
Caution
Caution
Terminal assignment
for controller with
4-wire connection
(to be preferred!)
Terminal assignment
for controller with
3-wire connection
Warning
DIL switch
Calibration