Data Sheet for Product

MXG461B Series Modulating Control Valve Technical Instructions
with Magnetic Actuator Document Number 125-4461
October 23, 2018
Siemens Industry, Inc. Page 3
Control
CAUTION:
You must use a four-wire connection with Vdc power supply.
Basic Diagram
Spring Return Action
LED
Indication
Operating State,
Function
Remarks, Troubleshooting
Green
Lit
Control mode
Normal operation; everything OK.
Flashing
Calibration
In manual control
Wait until calibration is finished
(green or red LED will be lit).
Hand wheel in Man or Off position.
Red
Lit
Calibration error
Internal error
Recalibrate (bridge contacts behind the
calibration slot).
Replace electronics module.
Flashing
Mains fault
DC Supply -/+
Check electric main network (outside the
frequency or voltage range);
Vdc supply +/- connection polarity.
Both
Dark
No power supply
Electronics faulty
Check electric main network, check wiring.
Replace electronics module.