Data Sheet for Product
5/14
Siem ens Modulating control valves with magnetic actuators, PN 16 CE2N4461en
Building Technologies 2018-02-05
If the electronics module is replaced or the actuator turned through 180 °, the valve’s
electronics must be recalibrated. For that, the hand wheel must be set to Auto.
The printed circuit board has a slot (position 3, preceding page).
Calibration is made by bridging the contacts located behind the slot using
a screwdriver. The valve will then travel across the full stroke to store the
end positions.
01124
While calibration is in progress, the green LED will flash for about 10 seconds (also refer
to «Indication of operating state»).
LED Indication Function Remarks, troubleshooting
Green Lit Control mode Normal operation; everything o.k.
Flashing Calibration
In manual control
Wait until calibration is finished
(green or red LED will be lit)
Hand wheel in Man or Off position
Red Lit Calibration error
Internal error
Recalibrate (bridge contacts behind the calibration
slot)
Replace electronics module
Flashing Mains fault
DC Supply - / +
Check mains network (outside the frequency or
voltage range)
DC supply + / - connection rectify
Both Dark No power supply
Electronics faulty
Check mains network, check wiring
Replace electronics module
Sizing
V
[
l
/
s
]
1
0
0
V
[
m
/
h
]
1
0
0
3
Χp
V100
= differential pressure across the fully open valve and the valve’s control path A ↑ AB by a
volume flow V
100
V
100
= volume flow through the fully open valve (H
100
)
Χpmax = max. permissible differential pressure across the valve’s control path for the entire actuating
range of the motorized valve
100 kPa = 1 bar ≡ 10 mWC
1 m
3
/h = 0,278 l/s water at 20 °C
Calibration
Indication of
operating state
Flow chart