Data Sheet for Product

Technical Instructions MXG461B Series Modulating Control Valve
Document Number 125-4461 with Magnetic Actuator
October 23, 2018
Page 8 Siemens Industry, Inc.
Specifications,
Continued
Pipe connections
Electrical connections
Ambient conditions
Agency approvals
Miscellaneous
Connection
Terminals
WARNING:
If the controller and the valve receive their power supply from separate
sources, the valve transformer must not be grounded on the secondary
side.
A four-wire connection is mandatory with DC power supply.
Controllers with:
0 to 10 Vdc
2 to 10 Vdc
0 to 20 mA
4 to 20 mA
Figure 12.
1. In case of strong vibrations, use high-flex stranded wires.