Indication of
oper
ating state
The two-color LED display indicating operating status can be viewed by opening the
cover of the electronics mod
ule.
LED Indication Function Remarks, troubleshooting
Green Lit
Control mode Automatic operation; everything o.k.
Flashing
Calibration
In manual control
Wait until calibration is finished
(green or red LED will be lit)
Hand wheel in MANUAL or OFF position
Red Lit
Calibration error
Internal error
Recalibrate (operate button in opening 1x)
Replace electronics module
Flashing
Mains fault Check mains network (outside the frequency or
voltage range)
Both Dark
No power supply
Electronics faulty
Check mains network, check wiring
Replace electronics module
As a general rule, the LED can assume only the states shown above (continuously red
or green, flashing red or green, or off).
Sizing
Flo
w chart
Δp
V
100
= differential pressure across the fully open valve and the valve’s control path A AB by a
volume flow
V
100
V
100
= volume flow through the fully open valve (H
100
)
Δpmax = max. permissible differential pressure across the valve’s control path for the entire actuating
range of the motorized valve
100 kPa = 1 bar 10 mWC
1 m
3
/h = 0.278 l/s water at 20 °C
Note for
media other
than water
When sizing valves for media other than water, note that the medium properties
specific heat
density
kinematic viscosity
differ from water. All variables depend on temperature. The design temperature is the
lowest medium temperature in the valve.
6/14
Siemens Modulating control valves with magnetic actuators, PN16 CA1N4455en