Siem ens Modulating control valves with magnetic actuators, PN 16 CA1N4455en
Building Technologies 2018-02-05
YF – Function
no function fully open closed
ConnectionsTransferFunction
YF not connected
valve will follow the Y-signal
YF connected to G
valve will fully open
control path A AB
YF connected to G0
valve will close control path
A AB
1. Hand wheel position MANUAL (open) or OFF (close)
2. Forced control signal YF
3. Signal input Y
The MX..461.. and MX..461..P magnetic valves are
factory-calibrated at 0 % and 100 % stroke.
When commissioning the valves, however, (especially
under extreme conditions of use) there may still be
some leakage via control path A AB with a 0 %
stroke control signal (DC 0 V, DC 2 V or DC 4 mA).
In this case, the valve can be recalibrated simply and
quickly:
1. Hand wheel [2] in AUTO-position
2. Use a pointed implement (ø 2 mm) to operate the
button in the opening [3] once
3. While recalibration is in progress, the LED [5] is
flashing green for approximately 10 seconds.
The valve will be briefly closed and fully opened.
If the electronics module is replaced, the valve’s
electronics must be recalibrated. For that, the hand
wheel must be set to AUTO.
Forced control input
YF
Signal priority
Calibration