Sizing
For accurate valve sizing, we recommend using the "Refrigeration VASP" software
sizing tool, available from your local Siemens office.
Engineering notes
Additional installation notes may also need be observed as well as the use of proper
safety elements (e.g. pressure switches, motor protection) depending on the particular
application.
In order not to damage the seal inside the valve insert, the plant must be vented on the
low-pressure side after the pressure test has been made (valve port AB), or the valve
must be fully open during the pressure test and during venting (power supply connect-
ed and positioning signal at maximum or forced opening by G ZC).
To prevent the formation of flash gas on expansion applications, the velocity of the
refrigerant in the fluid pipe must not exceed 1 m/s. To assure this, the diameter of the
fluid pipe must under certain circumstances be greater than the nominal size of the
valve.
1 = evaporator
2 = compressor
3 = condenser
4 = expansion valves
a) The differential pressure over reduction must be less than half the differential pres-
sure Δp
FL
.
b) The inlet path between diameter reduction and expansion valve inlet
ƒ Must straight for at least 600 mm
ƒ May not contain any valves
A filter / dryer must be mounted upstream of the expansion valve.
Warning
Expansion application
Engineering notes