Data Sheet for Product

7/20
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Smart Infrastructure 2021-08-02
Mounting notes
The valve should be mounted and commissioned by qualified staff. The same applies
to the replacement electronics and the configuration of the controller (e.g. SAPHIR or
PolyCool).
90°
4716Z16
90°
The refrigerant valves can be mounted in any orientation, but
upright mounting is preferable.
Arrange the pipework in such a way that the valve is not
located at a low point in the plant where oil can collect.
The pipes should be fitted in such a way that the alignment
does not distort the valve connections. Fix the valve body so
that that it cannot vibrate. Vibration can lead to burst
connection pipes.
Before soldering the pipes, ensure that the direction of flow
through the valve is correct.
The pipes must be soldered with care. To avoid dirt and the
formation of scale (oxide), inert gas is recommended for
soldering.
00441
The flame should be large enough to ensure that the junction
heats up quickly and the valve does not get too hot.
The flame should be directed away from the valve.
During soldering, cool the valve with a wet cloth, for example,
to ensure that it does not become too hot.
The valve body and the connected pipework should be
lagged.
The actuator must not be lagged.
The valve is supplied complete with mounting instructions 74 319 0232 0.
The refrigerant valve is maintenance-free.
The valve cannot be repaired. It has to be replaced as a complete unit.
Disposal
T
he valve is considered electrical and electronic equipment for disposal
in terms of the applicable European Directive and may not be disposed
of as domestic garbage.
Dispose of the valve through channels provided for this
purpose.
Comply with all local and currently applicable laws and
regulations.
Warranty
Observe all application-specific technical data.
If you ignore specified limits, Siemens will not assume any responsibility.
Maintenance
Repair