Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Smart Infrastructure 2021-08-02
Mounting notes
The valve should be mounted and commissioned by qualified staff. The same applies
to the replacement electronics and the configuration of the controller (e.g. SAPHIR or
PolyCool).
90°
4716Z16
90°
• The refrigerant valves can be mounted in any orientation, but
upright mounting is preferable.
• Arrange the pipework in such a way that the valve is not
located at a low point in the plant where oil can collect.
• The pipes should be fitted in such a way that the alignment
does not distort the valve connections. Fix the valve body so
that that it cannot vibrate. Vibration can lead to burst
connection pipes.
• Before soldering the pipes, ensure that the direction of flow
through the valve is correct.
• The pipes must be soldered with care. To avoid dirt and the
formation of scale (oxide), inert gas is recommended for
soldering.
00441
•
The flame should be large enough to ensure that the junction
heats up quickly and the valve does not get too hot.
• The flame should be directed away from the valve.
• During soldering, cool the valve with a wet cloth, for example,
to ensure that it does not become too hot.
• The valve body and the connected pipework should be
lagged.
• The actuator must not be lagged.
The valve is supplied complete with mounting instructions 74 319 0232 0.
The refrigerant valve is maintenance-free.
The valve cannot be repaired. It has to be replaced as a complete unit.
Disposal
T
he valve is considered electrical and electronic equipment for disposal
in terms of the applicable European Directive and may not be disposed
of as domestic garbage.
• Dispose of the valve through channels provided for this
purpose.
• Comply with all local and currently applicable laws and
regulations.
Warranty
Observe all application-specific technical data.
If you ignore specified limits, Siemens will not assume any responsibility.
Maintenance
Repair