User Guide

Mounting instructions
The valve should be mounted and commissioned by qualified staff. The same applies
to the replacement electronics and the configuration of the controller.
Comply with requirements per EN 60079-14 for use / installation.
Note additiona
l installation notes depending on application and use the appropriate
safety elements (e.g. pressure control, motor full protection).
90°
90°
00441
The refrigerant valves can be mounted in any orientation, but
upright mounting is preferable.
Arrange the pipework in such a way that the valve is not
located at a low point in the plant where oil can collect.
The pipes should be fitted in such a way that the alignment
does not distort the valve connections. Fix the valve body so
that that it cannot vibrate. Vibration can lead to burst
connection pipes.
Before soldering the pipes, ensure that the direction of flow
through the valve is correct.
The pipes must be soldered with care. To avoid dirt and the
formation of scale (oxide), inert gas is recommended for
soldering.
The flame should be large enough to ensure that the junction
heats up quickly and the valve does not get too hot.
The flame should be directed away from the valve.
During soldering, cool the valve with a wet cloth, for example,
to ensure that it does not become too hot.
Port B must be sealed off when a 2-port valve (AB A) is
used.
The valve body and the connected pipework should be lagged.
The actuator must not be lagged.
Connection terminals
6/12
Siemens Refrigerant Valves PS45 CE2Q4714en
Building Technologies 29.02.2012