Data Sheet for Product

9/14
Siem ens Modulating control valves with magnetic actuator, PN 16 CE1N4361en
Building Technologies 2018-02-05
Disposal
The device is considered electrical and electronic equipment for disposal
in terms of the applicable European Directive and may not be disposed
of as domestic garbage.
Dispose of the device through channels provided for this
purpose.
Comply with all local and currently applicable laws and
regulations.
Warranty
Application-specific technical data must be observed.
If specified limits are not observed, Siemens will not assume any responsibility.
Technical data
Functional data of actuator
Power supply For use with low-voltage only (SELV, PELV)
AC 24 V
Operating voltage
AC 24 V °20% (SELV) or
AC 24 V class 2 (US)
Frequency 45...65 Hz
Typical power consumption P
med
refer to «Connection type», page 8
Standby < 1 W (valve fully closed)
Rated apparent power S
NA
refer to «Connection type», page 8
Required fuse I
F
slow, «Connection type», page 8
External supply line protection
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
EN 60898
or
Power source with current limitation of
max. 10 A
DC 24 V
Operating voltage DC 20...30 V
Signal inputs
Control signal Y DC 0/2...10 V
or DC 0/4...20 mA
or phase cut signal DC 0...20 V Phs
Impedance DC 0/2...10 V 100 kς // 5nF (load < 0.1 mA)
DC 0/4...20 mA 240 ς // 5nF
Forced control Z
Impedance 22 kς
Closing the valve (Z connected to G0) < AC 1 V; < DC 0.8 V
Opening the valve (Z connected to G) > AC 6 V; > DC 5 V
No function (Z not wired up) phase-cut or control signal Y active
Signal outputs
Position feedback signal voltage DC 0/2...10 V; load resistance > 500 ς
current DC 0/4...20 mA; load resistance 500 ς
Stroke measurement
Nonlinearity
inductive
± 3 % of end value
Positioning time Positioning time < 2 s
Electrical connections Cable entries 2 x 20,5 mm (for M20)
Connection terminals screw terminals for 4 mm
2
wires
Min. wire cross-section 0.75 mm
2
Max. cable length refer to «Connection type», page 8