Data Sheet for Product

5/14
Siem ens Modulating control valves with magnetic actuator, PN 16 CE1N4361en
Building Technologies 2018-02-05
LED Indication Function Remarks, troubleshooting
Green Lit Control mode Normal operation; everything o.k.
Flashing Calibration
In manual control
Wait until calibration is finished
(green or red LED will be lit)
Hand wheel in Man or Off position
Red Lit Calibration error
Internal error
Recalibrate (bridge contacts behind the calibration
slot)
Replace electronics module
Flashing Mains fault
DC Supply - / +
Check mains network (outside the frequency or
voltage range)
DC supply + / - connection rectify
Both Dark No power supply
Electronics faulty
Check mains network, check wiring
Replace electronics module
Dimension
Working pressure [bar]
120
160
140
12
13
16
0
100
80
20
14
15
1
180
200
1
Medium temperature [°C]
Current local legislation must be observed.
Absolute working pressure [bar]
Medium temperature [°C]
W ater -
wet steam avoid
saturated steam
permissible range of use
superheated steam
Indication of
operating state
Working pressure and
medium temperature
Fluids
Saturated steam
Superheated steam