Data Sheet for Product
8/14
Siem ens Modulating control valves with magnetic actuator, PN 16 CE1N4361en
Building Technologies 2018-02-05
The 4-wire connection should always be given preference!
S
NA
P
MED
S
TR
P
TR
I
F
Wire cross-section [mm
2
]
1,5
2,5
4,0
Type reference
[VA]
[W]
[VA]
[W]
[A]
max. cable length L
[m]
MVF461H15-0.6
33
15 ″50
″50 3.15 60 100 160
MVF461H15-1.5
MVF461H15-3
MVF461H20-5
MVF461H25-8
MVF461H32-12
43 20 ″75
″70
4 40 70 120
MVF461H40-20
65 26 ″100 6.3 30 50 80
MVF461H50-30
S
NA
= nominal apparent power
P
med
= typical power consumption in the application
S
TR
= Minimum apparent transformer power
P
TR
= Minimum DC supply power
I
F
= Minimal required slow fuse
L = max. cable length; with 4-wire connections, the max. permissible length of the separate
1.5 mm
2
copper positioning signal wire is 200 m
1)
All information at AC 24 V or DC 24V
Mounting notes
The valve is supplied complete with Mounting Instructions 74 319 0378 0.
The valve may only be used in flow direction (A ⇓ AB).
Observe the direction of flow!
90°
446 1Z16
90°
IP31
IP31
Installation notes
∂ The actuator may not be lagged
For electrical installation, refer to «Connection diagrams».
Maintenance notes
The low friction and robust, maintenance-free design makes regular servicing
unnecessary and ensure a long service life.
The valve stem is sealed from external influences by a maintenance-free gland.
If the red LED is lit, the electronics must be recalibrated or replaced.
Should the valve electronics prove faulty, the ASE12 electronics module must be
replaced (refer to Mounting Instructions 74 319 0404 0).
Always disconnect power before fitting or removing the electronics module.
After replacing the electronics module, calibration must be triggered in order to
optimally match the electronics to the valve (refer to «Calibration»).
Connection type
1)
4-wire connection
Caution
Mounting position
Repair
Caution