Data Sheet for Product

Technical Instructions MVF461H Series Modulating Control Valve
Document Number 125-4361 with Magnetic Actuator
June 17, 2008
Page 6 Siemens Building Technologies, Inc.
Characteristic
SSEN0343R1
10 [V]
10 [V]
20 [mA]
86420
2
4
100
80
60
40
20
0
[%]
90063
6
12
V
Figure 8. Equal Percentage.
SSEN0344R1
10 [V]
10 [V]
20 [mA]
86420
2
4
100
80
60
40
20
0
[%]
90064
6
12
V
Figure 9. Linear.
Installation Notes
Installation instructions for the valve and terminal housing are enclosed with the valve.
For electrical installation, see Wiring Diagrams.
CAUTION:
Always disconnect the power before fitting or removing the terminal
housing. The terminal housing is calibrated and matched to the actuator,
and should be replaced only by qualified personnel.
Valve may only be used in flow direction (A AB). Note the flow
direction.
Do not allow the surface temperature of the actuator to fall below the
dew point temperature of the surrounding air (causing condensation).
If necessary, insulate the valve. Do not insulate the actuator.
Mounting Position
Vertical to horizontal mounting:
Do not mount the valve below horizontal.
SSEN0345R1
90 90
IP31IP31
Figure 10. Acceptable Mounting
Positions.
Specifications
Electrical
Low-voltage use only Class 2 (SELV, PELV)
24 Vac
Operating voltage 24 Vac +20/-15%
Frequency 45 to 65 Hz
Typical power consumption See Table 1, P
med
Standby <1 W (valve fully closed)
Nominal apparent power See Table 1, S
NA
Suitable fuse Slow, see Table 1, I
N
24 Vdc
Operating voltage 20 to 30 Vdc