Specification

Rainproof Combination Metering
General Information:
Circuit Breakers overload trip position is indicated by
handle position midway between ON and OFF. To reset,
move handle to OFF position then turn ON.
For installation in accordance with all local Electrical codes
and/or the National Electrical Code .
Short Circuit Current Rating (Watthour Meter not included in short circuit rating)
This panelboard has a Siemens Type QNH or MD-HT (rated 22k AIC) circuit breaker installed and has a maximum short circuit
rating of 22,000 RMS symmetrical amperes, 120/240 volts ~. The actual rating is equal to the lowest rating of any breaker
installed. If the circuit breaker is replaced, use only Siemens Type QNH or MD-HT.
Siemens Energy & Automation, Inc.
Alpharetta, Georgia U.S.A.
Part No. 4099606 Rev B
Important
This equipment has been designed for use only with Siemens Type QNH or MD-HT Circuit Breakers. Use of
other circuit breakers in this equipment will void the warranty.
Do not spray or allow any petroleum based chemicals, solvents, or paint to contact interior components.
The National Electrical Code is a recognized trademark of NFPA.
275 lb in250 kcmil- #4N3
120 lb in1/0-#14N4
275 lb in250 kcmil - #6N2
50 lb in
45 lb in
40 lb in
35 lb in
#2-#3
#4-#6
#8
#10-#14
N1
275 lb in250 kcmil - #6A, B
TorqueWire SizeTerminal
J2
E10703
AB
N1
N2
N3 N4
BONDED
NEUTRAL
SERVICE
DISCONNECT
Enclosure
Type 3R
Catalog number
MM0202B1200R
Panelboard Rating
200 Amps, Max
120/240 Volts ~, 1 phase, 3 wire
208Y/120 Volts ~, 1 phase, 3 wire
(Derived from 3 phase – 4 wire system)
Meter Socket Rating
200 Amps Continuous
Suitable Only For Use As
Service Equipment
For Overhead or Underground
Service
Use 60/75° C Copper or
Aluminum Conductor
in Terminals
A, B, N1, N2, N3, and N4.
Main Breaker Terminals
See markings on breaker for torque
requirements and conductor rating
Assembled in Mexico
If hub is required, the catalog numbers listed below
may be used on this enclosure
Trade size (in) Catalog number
1 ¼” S38597-2
1 ½” S38598-2
2” S38599-2
2 ½ S38600-2

Summary of content (1 pages)