User Manual
5 / 16
Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
Override control input can be operated in following different modes of operation
Z-mode
no function
fully open
closed
override with 0…1000 Ω
Connections
Transfer
linear or equal-percentage
linear or equal-percentage
• Z-contact not connected
• Valve stroke follows Y-
input
• Z-contact connected
directly to G
• Y-input has no effect
• Z-contact connected
directly to G0
• Y-input has no effect
• Z-contact connected to M
via resistor R
• Starting position at 50 Ω /
end position at 900 Ω
• Y-input has no effect
Shown operation modes are based on the factory setting «direct acting»
Y-input has no effect in Z-mode.
Accessories
ASC9.3
double auxiliary switch
ASZ7.3..
potentiometer
adjustable switching points
ASZ7.3: 0…1000 Ω
ASZ7.31: 0…135 Ω
ASZ7.32: 0…200 Ω
ASC1.6
Auxiliary switch
Switching point 0...5 % stroke
Override control
input Z
MK..662..
Note
MK..632..
MK..662..