User Manual

4 / 16
Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
Positioning signal Y
Position feedback U
Flow characteristic
ON
ON
1 2
4567Z05
DC 4…20 mA
ON
21
4567Z07
lin = linear
OFF *)
ON
1 2
4567Z06
DC 0…10 V
ON
21
4567Z08
log = equal-percentage
*) Factory setting: All switches OFF
Relationship
between control
signal Y and
volumetric flow
0
4
l
i
n
l
o
g
V
100
V
0
10 V
20 mA
In order to determine the stroke positions 0 % and 100 % in the valve, calibration is
required on initial commissioning:
Prerequisites
AC 24 V power supply
Red safety clamp has to be removed, see commissioning notes .
Housing cover removed
Calibration
1. Short-circuit contacts in calibration slot
(e.g. with a screwdriver)
2. Actuator moves to «0 %» stroke position (1)
(valve closed)
3. Actuator moves to «100 %» stroke position (2)
(valve open)
4. Measured values are stored
01124
green LED flashes;
position feedback
U inactive
0%
t
100%
Stroke
1
2
3
4567Z09
Normal operation
5. Actuator moves to the position (3) as
indicated by signals Y or Z
green LED is lit permanently;
position feedback U active, the values
correspond to the actual positions
A lit red LED indicates a calibration error.
The calibration can be repeated any number of times.
The LED status indication indicates operational status and is visible with removed
cover.
LED
Indication
Function
Remarks, troubleshooting
Green
Lit
Normal operation
Automatic operation; everything o.k.
Flashing
Calibration in progress
Wait until calibration is finished (LED stops
flashing, green or red LED will be lit)
Red
Lit
Faulty stroke calibration
Check mounting
Restart stroke calibration (by short-circuiting
calibration slot)
Internal error
Replace electronics
Flashing
Inner valve jammed
Check valve
Both
Dark
No power supply
Electronics faulty
Check mains network, check wiring
Replace electronics
As a general rule, the LED can assume only the states shown above (continuously
red or green, flashing red or green, or off).
Stroke calibration
MK..662..
Indication of
operating state
MK..662..