Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
Type summary
Control device
MKB632.., MKC632..
Operating voltage
Positioning signal
Electrohydraulic actuator 2800 N, 120 s
AC 230 V
2-port valve
3-position
p
max
p
s
DN
k
vs
S
v
Product number
Stock number
Product number
Stock number
[kPa]
[kPa]
[m
3
/ h]
MKB632.15-0.19
2)
S55329-M180-A110
MKB662.15-0.19
2)
S55329-M180-A111
1600
1)
3200
15
0,19
> 50
MKB632.15-0.3
2)
S55329-M181-A110
MKB662.15-0.3
2)
S55329-M181-A111
0,3
MKB632.15-0.45
2)
S55329-M182-A110
MKB662.15-0.45
2)
S55329-M182-A111
0,45
MKB632.15-0.7
2)
S55329-M183-A110
MKB662.15-0.7
2)
S55329-M183-A111
0,7
MKB632.15-1.2
2)
S55329-M184-A110
MKB662.15-1.2
2)
S55329-M184-A111
1,2
MKB632.15-1.9
2)
S55329-M185-A110
MKB662.15-1.9
2)
S55329-M185-A111
1,9
MKB632.15-3
2)
S55329-M186-A110
MKB662.15-3
2)
S55329-M186-A111
3
MKB632.25-5
2)
S55329-M187-A110
MKB662.25-5
2)
S55329-M187-A111
25
5
MKB632.25-7.5
2)
S55329-M188-A110
MKB662.25-7.5
2)
S55329-M188-A111
7,5
> 100
MKB632.40-12
2)
S55329-M189-A110
MKB662.40-12
2)
S55329-M189-A111
40
12
> 50
MKB632.40-19
2)
S55329-M190-A110
MKB662.40-19
2)
S55329-M190-A111
19
MKB632.50-31
2)
S55329-M191-A110
MKB662.50-31
2)
S55329-M191-A111
50
31
> 100
MKC632.65-49
2)
S55329-M192-A120
MKC662.65-49
2)
S55329-M192-A121
1000
1)
3200
65
49
> 100
MKC632.80-78
2)
S55329-M193-A120
MKC662.80-78
2)
S55329-M193-A121
700
1)
80
78
MKC632.100-124
2)
S55329-M194-A120
MKC662.100-124
2)
S55329-M194-A121
450
1)
100
124
MKC632.125-200
2)
S55329-M195-A120
MKC662.125-200
2)
S55329-M195-A121
300
1)
125
200
MKC632.150-300
2)
S55329-M196-A120
MKC662.150-300
2)
S55329-M196-A121
200
1)
150
300
1)
Permissible working pressure and medium temperature for steam refer to diagram page 7 and 10
2)
While stocks last
DN = Nominal size
k
vs
= Nominal flow rate of cold water (5…30 °C) through the fully open valve (H
100
) by a differential
pressure of 100 kPa (1 bar)
S
v
= Rangeability k
vs
/k
vr
k
vr
= Smallest k
v
value, at which the flow characteristic tolerances can still be maintained, by a differ-
ential pressure of 100 kPa (1 bar)
Product number
Description
For control devices
Mounting location
ASC1.6
Auxiliary switch
MKB662.., MKC662..
1 x ASC 1.6
ASC9.3
Dual auxiliary switches
MKB632..
MKC632..
1 x ASC9.3 or
1 x ASZ7.3 or
1 x ASZ7.31 or
1 x ASZ7.32
ASZ7.3
Potentiometer 1000 Ω
ASZ7.31
Potentiometer 135 Ω
ASZ7.32
Potentiometer 200 Ω
Ordering
Prior delivery valve and actuator are preassembled. The control device is preset to
50 % stroke. Accessories are packed and supplied separately
No spare parts available. The control device has to be replaced as a whole unit
else TÜV approval for the safety function to DIN EN 14597 ceases.
Accessories
Product number
Stock number
Designation
MKC632.80-78
S55329-M193-A120
Control device PN25, safety function to DIN EN 14597
Delivery