User Manual
13 / 16
Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
MKB632..
MKC632..
MKB662..
MKC662..
Max. Power consumption at 50 Hz
MKB632..: 15 VA / 13 W
MKC632..: 24 VA / 21 W
MKB662..: 17 VA / 12 W
MKC662..: 24 VA / 18 W
External supply cable fuse
min. 0.5 A, slow
max. 6 A, slow
MKB662..: min. 1 A, slow
max. 10 A, slow
MKC662..: min. 1,6 A, slow
max. 10 A, slow
Signal inputs
Control signal Y
3-position
DC 0...10 V, DC 4...20 mA
or 0...1000 Ω
Signal inputs
Terminal Y
Voltage
DC 0…10 V
Input impedance
100 kΩ
Current
DC 4…20 mA
Input impedance
240 Ω
Signal resolution
< 1%
Hysteresis
1 %
Override control Z
Resistor
1000 Ω
Z not connected
No function, priority termi-
nal Y
Z connected directly to G
max. stroke 100 %
Z connected directly to G0
min. stroke 0 %
Z connected to M via 0...1000
stroke proportional to R
Signal outputs
Position feedback U
voltage
DC 0...9.8 V ±2 %
load impedance
> 10 kΩ
current
DC 4...19.6 mA ±2 %
load impedance
< 500 Ω
Operating data
Positioning time at 50 Hz
opening
120 s
120 s
closing
120 s
10 s
20 s
Spring-return time
(closing)
5…25 s
Nominal stroke
20 mm
40 mm
20 mm
40 mm
Max. permissible medium temper-
ature
+1…220 °C
El. Connections
Cable entry
4 x M20 ( 20.5 mm)
Materials
Actuator housing, bracket
Die-cast aluminum
Housing box and
manual adjuster
Plastic
Dimensions
Dimensions
Refer to "Dimensions", page 16
Weights
Refer to "Dimensions", page 16
Norms
CE-conformity
EMC-directive
2004/108/EC
Immunity
EN 61000-6-2 Industrial
Emission
EN 61000-6-3 Residential
Low voltage directive
2006/95/EC
Electrical safety
EN 60730-1
Product standards for automatic
electric controls
EN 60730-2-14
Control device with safety function
DIN EN 14597
Temperature control devices and temperature
limiters for heat generating systems; Actuator devices with safe-
ty functions in heat generating systems
MKB.. Registration no.: 1F137/10
MKC.. Registration no.: 1F138/10
Protection standard EN 60730
I
III
Housing protection standard
Upright to horizontal
IP54 to EN 60529
Conform with C-tick
N474