User Manual

12 / 16
Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
Disposal
The device contains electrical and electronic components and must not be dis-
posed of together with domestic waste. This applies in particular to the PCB.
Before disposal the valve must be dismantled and separated into its various con-
stituent materials.
Legislation may demand special handling of certain components, or it may be sen-
sible from an ecological point of view.
Current local legislation must be observed.
Warranty
The technical data relating to specific applications are valid only in conjunction with
the control devices listed in this data sheet under «Type summary», page 2.
Approval as actuating device with safety function as per DIN EN 14597 ap-
plies to the entire actuator. Approval as actuating device with safety function
as per DIN EN 14597 expires if the actuator is separated from the valve. This
also voids any guarantees on the part of Siemens Switzerland Ltd.
Technical data
MKB632..
MKC632..
MKB662..
MKC662..
Valve
PN class
PN 40 to ISO 7268
Working pressure
to ISO 7005 within the permissible working pressure and medi-
um temperature according to the diagram on page 8
Flow characteristic
0…30 %
30…100 %
linear
equal percentage; n
gl
= 3 to VDI / VDE 2173
Leakage rate
0…0.05 % of k
vs
value to DIN EN 1349
Permissible media:
Water
cooling water, chilled water, low temperature hot water, high
temperature hot water, water with anti-freeze;
recommendation: water treatment to VDI 2035
Brine
Steam
saturated steam, super-heated steam;
dryness at inlet minimum 0.98
Heat transfer oils
Medium temperature
Water, brine
steam DN15…25
DN 40…150
Heat transfer oils
+1…220 °C
220 °C, 1700 kPa (17 bar) abs
220 °C, 1100 kPa (11 bar) abs
Permissible working pressure and medium temperature refer to
diagram page 7 and 10
220 °C
Rangeability S
v
DN 15…40: > 50 (MK..6..25-7.5: > 100)
DN 50…150: > 100
Materials
Valve body
cast steel GP240GH
Stem
Stainless steel
Plug, seat
Stainless steel
Sealing gland
Stainless steel
Gland materials
PTFE sleeve
Actuators
Power supply
Operating voltage
Voltage tolerance
AC 230 V
15 %
AC 24 V
20 % / +30 %
SELV / PELV
Frequency
50 or 60 Hz